Is the AS-Interface cable (yellow and black) silicone-free ?

  • The cable is silicone screting free.

Is the AS-Interface flat cable halogen-free ?

  • Yes, the sheething consists of a halogen-free rubber mixture (EM3) in accordance with VDE 0207 Part 31.

How can you expand an AS-Interface network ?

  • With repeaters and / or extenders.

Is it possible to mix the operation of AS-Interface slaves to
specification 2.0 and 2.1 on the same line ?

  • Yes

Do AS-Interface applications require the use of a special AS-Interface power supply unit ?

  • Yes

Are the AS-i modules from the EM2 series still available?

  • No, click the question to obtain more infos.

How many LE4-505-BS1 and CM4-505-GS1 AS-Interface masters can be connected to a PS4-... ?

  • Click on the question to obtain information.

How many stations can be connected to an AS-Interface master LE4-505-BS1 and CM4-505-GS1 ?

  • 31 stations.

How many stations can be connected to an AS-Interface master CM4-505-GV1 and CM4-505-GV2 ?

  • 62 stations.

What is the name of the manual for AS-i Profibus-Gateways (CM4-505-GV1/GV2) ?

  • The article-number is AWB2700-1409-GB.
    The manual is available on the Moeller homepage => support => Quick Search to: CM4-505.

What is the name of the configuration software for the AS-i safety monitor?

  • AS4-505-CF1

What are the type designations for the AS-i safety monitors:
a) 1-channel; b) 2-channel?

  • a) AS4-505-MO1 b) AS4-505-MO2

What is the name of the download cable for the safety configuration of the PC in the AS-i safety monitor?

  • You need the cable ZB2-505-KB1, to download the safety configuration from the PC to the safety monitor.

What is the name of the data exchange cable (SM - SM) of the safety configuration for one safety monitor to another safety monitor ?

  • ZB2-505-KB2

Is there any particular PLC required for AS-i safety control ?

  • No, the safety control system is implemented using a additional safety monitor (AS4-505-MO1/-MO2).

After a new configuration, the AS-Interface monitor cannot be switched to protection mode and signals the entry of an incorrect password. Why ?

  • A new password must be defined. The preset password of the safety monitor is SIMON. After an application has been created, however, a new password that is different to SIMON must be defined in order to enable protection mode.

Can a safety slave (AS-Interface) be assigned to several safety monitors ?

  • When a monitor is configured, it is assigned with the safety slaves required for the application. It does not matter whether these slaves are also used by another monitor.

What reaction time can be reached with AS-Interface Safety at Work ?

  • The max. reaction time of AS-Interface Safety at Work is 40 ms.

Can safety information be transferred via the AS-Interface ?

  • The use of electronic devices for safety applications is permissible if the same level of safety is to be achieved as for conventional devices. For AS-Interface safety at work, this must be certified with the relevant test certificates.

Can a faulty safety AS-i slave exchanged without a new configuration of the safety monitor ?

  • Yes, please click on the question to obtain further information.