xEnergy switchboard systems up to 5000 A – product features

  • Enclosures for side-by-side and stand-alone cabinets
  • Degree of protection IP31 or IP55
  • Main busbars up to 5000 A
  • 2 Main busbar systems are possible in each section
  • Clear separations into functional areas from form 1to form 4 to provide even better protection for people and equipment
  • Widths of 425, 600, 800, 850, 1000, 1100, 1200and 1350 mm
  • Height 2000 mm
  • Color RAL 7035 (other colors upon request)
  • Network types TN-C, TN-C-S, TN-S, TT, IT
  • Type-tested switchgear assembliesin accordance with IEC/EN 61439
  • Optimized for 3 and 4 pole switchgear from Eaton

XP – Power sections
  • Incoming supplies, outgoers and couplings up to 5000 A
  • Cable connection from the top and bottom
  • Busbar positions rear-mounted - bottom/top mounted or running under the top panel
  • Section height 2000 mm / section depth 400/600/800/1000 (1000 = 800+200) mm
  • Internal separations up to Form 4
XF – Fixed
  • Power outgoers with circuit breakers and fuse switch disconnectors up to 630 A
  • Individual outgoers, such as controlgear, motor starters, small power outgoers etc.
  • For busbar positions at the rear - top/bottom or running under the top panel
  • Section height 2000 mm / section depth 600/800 mm
  • Internal separation up to form 4
XR – Removable
  • Power outgoers with circuit breakers and strip type switch-disconnector-fuse, up to 630 A
  • Empty modules for individual applications
  • Plug-in modules and strip type switch-disconnector-fuse can be replaced under live-line working conditions
  • Internal separation up to form 4
  • Easy maintenance and reduced down times
XW – Outgoing sections – withdrawable design
  • Widths of 1000/1200 mm
  • Section depths of 600/800/1000 mm
  • 3 or 4 poles
  • Rated current of dropper bars In=1000 or 2000 A / 3 or 4 poles
  • Max. short-circuit current ICW=80 kA
  • IP31/55
  • Shelf-boards can be mounted at individual heights, depending on the size of the modules
  • Max. height of dropper bar available to accommodate equipment = 1875 mm
  • Cable connection area, fully sealed off from the switchgear area, main busbar area and dropper bar area
  • Dropper bar at the front fully sealed off thanks to self-closing shutters
  • Drawers available:
    • Power outgoers up to 630 A
    • Direct starters from 0.06-132 kW
    • Reverse starters from 0.06-132 kW
    • Star-triangle starters from 5.5-110 kW
    • Outgoers from 132 to 250 kW are executed as fixed design solutions
XG – General – Empty sections for individual mounting units
  • Power factor corrections
  • Fitting systems for sub-distribution with devices for modular installation
  • Control technology with SASY 60i and xStart - suitable for installation of mounting plates as high as the section, or of split ones
  • Individual mounting units fixed on mounting plates
  • Section height 2000 mm
  • Section depths of 400/600/800 mm
  • Section widths of 425/600/800/850/1000/1100/1200/1350 mm
  • IP31/55