MFD-Titan: Input/output modules with temperature measurement

input/output modules with temperature measurement Using the temperature modules MFD-TP…/MFD-TAP… you can now directly connect PT100 and NI1000 temperature sensors directly to the MFD-Titan. Thus, the indirect method utilising an expensive temperature measurement amplifier is avoided.

The temperatures are measured with a 12 bit resolution and can be assigned to temperature ranges from -200 °C to 850 °C.

MFD-TP…You also have the option of selecting 2-wire or 3-wire connection of temperature sensors.

Programming is implemented in the usual manner using the wiring diagram entry via the EasySoft programming software.

Technical data

Analog inputs for Pt100 or Ni1000 resistance temperature sensors
Quantity 2 x Pt100 or 2 x Nt1000 (depending on the type)
Resistance sensor input type
– Platinum sensor Pt100 according to
   DIN EN 60751, IEC 751

– Nickel sensor Ni1000 according to
   DIN 43760

Temperature ranges
Pt100, range A, selectable °C, (°F) -40 to +90, (-40 to 194); 0 to 250,
(32 to 482); 0 to 400, (32 to 752)
Ni1000, range A, selectable °C, (°F) -40 to +90, (-40 to 194); 0 to 250, (32 to 482)
Pt100, range B
°C, (°F)
0 to 850, (32 to 1562); -200 to 200,
(-328 to 392)
Digital resolution, scaling per sensor
With operand „IA“ and „MD“,
   selectable under scalling
Bit 12 (0 to 4095)
With operand "MD",
   selectable under scaling
°C, (°F)
1, 0,1, (1), (0,1)
Measurement method Selectable two wire or three wire per sensor, using the sensor connections